Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 2, 2022, 10:16 AM
  • 18 0409_18 0408_03022022_032436.mp4

Date
03/02/2022
W/O
941501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00699
PipeID
P14244
Time
2:16 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9893
Sewer Name
18 SANTA FE STREET RELIEF TRUNK
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_941501_TV18173_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0409
Downstream MH
18 0408
Dir. of Survey
Downstream
Length Surveyed
127.3 ft.
Total Length
127.3 ft.
Structural Index
3
Structural Quick
413D
Structural Rating
131
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
139
Pipe schematic from manhole 18 0409 to 18 0408
MH: 18 0409MH: 18 0408downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04090 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - MAG COAT2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 8"56.6 ft. CS - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES100.5 ft. RFB - Roots Fine Barrell, from 09 to 03 o'clock, Start121.8 ft. RFB - Roots Fine Barrell, from 09 to 03 o'clock, Finish121.8 ft. FM - Fracture Multiple, from 04 to 09 o'clock, within 8 inches of joint: YES127.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0408127.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish127.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (7)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2.5 ft. - General Observation - MAG COAT

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 8"

    7.3 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 8"

  • Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

    56.6 ft. - Crack Spiral, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Barrell, from 09 to 03 o'clock, Start

    100.5 ft. - Roots Fine Barrell, from 09 to 03 o'clock, Start

  • Fracture Multiple, from 04 to 09 o'clock, within 8 inches of joint: YES

    121.8 ft. - Fracture Multiple, from 04 to 09 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
121.8RFB
7.3TB
2.5SSS
56.6CS
0AMH18 0409
0MWM
2.5MGOMAG COAT
100.5RFB
121.8FM
0MWL
2.5SAV
127.3AMH18 0408
127.3SSS
127.3SAV

Properties (7)

additional_info
630074030122203
custom_field_three
MAG COAT, AGGREGATE VISIBLE, SPALLING
custom_field_two
3
customer
1
datetime
2022-03-02T02:16:32-08:00
documentation
PRO PIPE
is_lateral_inspection
false