Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2022, 10:04 AM
  • 29 0342_29 0341_02182022_032742.mp4

Date
02/18/2022
W/O
941464
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01017
PipeID
P24362
Time
2:04 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9741
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_941464_TV29105_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0341
Downstream MH
29 0342
Dir. of Survey
Upstream
Length Surveyed
314.6 ft.
Total Length
314.6 ft.
Structural Index
3
Structural Quick
3J22
Structural Rating
169
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
172
Pipe schematic from manhole 29 0341 to 29 0342
MH: 29 0341MH: 29 0342upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 03420.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish16.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS22.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"55.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"114.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"120 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"147.4 ft. TBI - Tap Break-In Intruding, at 09 o'clock, -, -, within 8 inches of joint: YES, 6", 1"179.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"221.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"238.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"245.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"273.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start279.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES295.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"303.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES314.6 ft. AMH - Downstream Manhole, Survey Begins - 29 0341314.6 ft. MWL - Water Level, 5 %of cross sectional area314.6 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (5)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    10.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    35.5 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    41.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    69.1 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In Intruding, at 09 o'clock, -, -, within 8 inches of joint: YES, 6", 1"

    167.2 ft. - Tap Break-In Intruding, at 09 o'clock, -, -, within 8 inches of joint: YES, 6", 1"

Observations (19)

DistanceCodeObservation
167.2TBI
35.5CL
69.1TB
194.6TFC
0AMH29 0341
314.5CM
41.1CM
297.8TFDEBRIS
200.2TFC
75.7TFC
259.5TF
0MWL
0MWM
292.5TF
19.3TFC
314.6AMH29 0342
134.8TFC
10.9CL
93.4TF

Properties (7)

additional_info
630074021722202
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-18T02:04:49-08:00
documentation
PRO PIPE
is_lateral_inspection
false