Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2022, 08:43 AM
  • 29 0337_29 0322_02182022_020445.mp4

Date
02/18/2022
W/O
941464
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z01017
PipeID
P24356
Time
12:43 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9741
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_941464_TV29105_MAR2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0337
Downstream MH
29 0322
Dir. of Survey
Downstream
Length Surveyed
321.1 ft.
Total Length
321.1 ft.
Structural Index
3
Structural Quick
413L
Structural Rating
198
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
198
Pipe schematic from manhole 29 0337 to 29 0322
MH: 29 0337MH: 29 0322downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 03370 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 5 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"49.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"61.1 ft. CL - Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES80.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS144.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS172.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS202.7 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"246.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS256.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS283.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES321.1 ft. AMH - Downstream Manhole, Survey Ends - 29 0322321.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    24.2 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES

    61.1 ft. - Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"

    202.7 ft. - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 6"

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    283.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
202.7TBA
0AMH29 0337
144.1TFDEBRIS
24.2TB
0MWM
321.1AMH29 0322
321.1SAV
321.1MGOCONNECTION AT THE MH 9 OC'LOCK
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
283.2FM
256.5TFDEBRIS
61.1CL
49.6TF
246.2TFDEBRIS
80.2TFDEBRIS
2.3SAV
172.4TFDEBRIS

Properties (7)

additional_info
630074021722202
custom_field_three
FRACTURES, CRACKS, AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-02-18T00:43:47-08:00
documentation
PRO PIPE
is_lateral_inspection
false