Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2022, 06:28 AM
  • 29 0162_29 0161_02022022_224505.mp4

Date
02/02/2022
W/O
936272
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00354
PipeID
P24058
Time
10:28 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9859
Sewer Name
29 28TH STREET TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
WO_936272_TV29009_FEB2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
29 0162
Downstream MH
29 0161
Dir. of Survey
Downstream
Length Surveyed
278.8 ft.
Total Length
278.8 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
2
O&M Quick
412U
O&M Rating
224
Overall Index
2
Overall Quick
Overall Rating
389
Pipe schematic from manhole 29 0162 to 29 0161
MH: 29 0162MH: 29 0161downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 01620 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start88 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - CAPPED OR NOT, ETC..., SIZE - UNKNOWN (TAP WAS "PASSED-BY").140.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"189.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"237.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"278.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish278.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish278.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish278.6 ft. MGO - General Observation - COCKROACHES IN MH278.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0161

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    278.6 ft. - General Observation - COCKROACHES IN MH

Observations (15)

DistanceCodeObservation
0MWL
0AMH29 0162
278.2CM
237.3TF
278.8AMH29 0161
278.2DAGS
140.3TFC
2DAGS
278.6MGOCOCKROACHES IN MH
189.2TFC
2CM
88TFCAPPED OR NOT, ETC..., SIZE - UNKNOWN (TAP WAS "PASSED-BY").
2DAE
278.2DAE
0MWM

Properties (7)

additional_info
630138020222201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-02-02T22:28:47-08:00
documentation
PRO PIPE
is_lateral_inspection
false