Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2022, 05:53 AM
  • 18 1049_18 1048_02282022_231723.mp4

Date
02/28/2022
W/O
941485
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00678
PipeID
P14903
Time
9:53 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9749
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 2A
City
WHIITIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_941485_TV18015_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
18 1049
Downstream MH
18 1048
Dir. of Survey
Downstream
Length Surveyed
348.4 ft.
Total Length
348.4 ft.
Structural Index
3
Structural Quick
423K
Structural Rating
192
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
195
Pipe schematic from manhole 18 1049 to 18 1048
MH: 18 1049MH: 18 1048downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 18 10490 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area7.1 ft. CM - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES10.4 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES14 ft. CL - Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES38.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"50.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"52.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"114.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"132.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"143.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"188.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"212.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"240.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"242.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"256.5 ft. FM - Fracture Multiple, from 03 to 07 o'clock, within 8 inches of joint: YES257.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"290.9 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6"295.4 ft. FM - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES332.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"341.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"348.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.4 ft. AMH - Downstream Manhole, Survey Ends - 18 1048

Observation photos (10)

  • Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES

    7.1 ft. - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    10.4 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES

    14 ft. - Crack Longitudinal, at 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    52.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    89.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    132.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    240.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Fracture Multiple, from 03 to 07 o'clock, within 8 inches of joint: YES

    256.5 ft. - Fracture Multiple, from 03 to 07 o'clock, within 8 inches of joint: YES

  • Tap Break-In Defective, at 10 o'clock, -,  , within 8 inches of joint: YES, 6"

    290.9 ft. - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6"

  • Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

    295.4 ft. - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
14CL
256.5FM
290.9TBD
0MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
52.1CM
7.1CM
89.9TB
0AMH18 1049
0MWM
332.8TF
0MWL
212.5TF
240.9TB
10.4CL
38.8TFC
188.8TFC
114.1TF
341.4TFC
348.4CM
348.4AMH18 1048
50.7TF
295.4FM
257.7TFA
143.8TF
132.9TB
242.7TF

Properties (7)

additional_info
630074022822201
custom_field_three
CRACKS, FRACTURES
custom_field_two
2
customer
1
datetime
2022-02-28T21:53:48-08:00
documentation
PRO PIPE
is_lateral_inspection
false