Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 7, 2022, 09:59 AM
  • 18 0374_18 0373_03072022_030917.mp4

Date
03/07/2022
W/O
941471
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00690
PipeID
P14208
Time
1:59 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9912
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_941471_TV18095_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0374
Downstream MH
18 0373
Dir. of Survey
Downstream
Length Surveyed
323.7 ft.
Total Length
323.7 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
252
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
252
Pipe schematic from manhole 18 0374 to 18 0373
MH: 18 0374MH: 18 0373downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 18 03740 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED3.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start90.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"205.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"315.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"319.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish323.7 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK323.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0373

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
319.7FM
90.6TFA
205.9TFC
0MWM
315.8TF
0MWL
0MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
3.9FM
0AMH18 0374
0MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
323.7MGOCONNECTION AT THE MH 9 OC'LOCK
323.7AMH18 0373

Properties (7)

additional_info
630074030722001
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-03-07T01:59:08-08:00
documentation
PROPIPE
is_lateral_inspection
false