Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2022, 07:38 AM
  • 18 0989_18 0988_03012022_004725.mp4

Date
02/28/2022
W/O
941291
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00677
PipeID
P14843
Time
11:38 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9750
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 1
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_941291_TV18116_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
18 0989
Downstream MH
18 0988
Dir. of Survey
Downstream
Length Surveyed
148.6 ft.
Total Length
148.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
411B
O&M Rating
18
Overall Index
1
Overall Quick
Overall Rating
18
Pipe schematic from manhole 18 0989 to 18 0988
MH: 18 0989MH: 18 0988downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 098971.8 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES81.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start148.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0988148.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

    71.8 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    81.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
148.6AMH18 0988
0MGOCONNECTION AT THE MH 9 OC'LOCK
148.6RFJ
71.8RFJ
81.8RFJ
0MWM
0MWL
0AMH18 0989

Properties (7)

additional_info
630074022822202
custom_field_three
NO STRUCTURAL DEFECTS
custom_field_two
4
customer
1
datetime
2022-02-28T23:38:04-08:00
documentation
PRO PIPE
is_lateral_inspection
false