Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2022, 10:31 AM
  • J 0156_J 0155_02112022_023812.mp4

Date
02/11/2022
W/O
936261
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00055
PipeID
P11396
Time
2:31 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9734
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
RANCHO PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
40
Purpose
Routine Assessment
Project
WO_936261_TV05161_FEB2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
J 0155
Downstream MH
J 0156
Dir. of Survey
Upstream
Length Surveyed
119.7 ft.
Total Length
119.7 ft.
Structural Index
2
Structural Quick
2D00
Structural Rating
48
O&M Index
2
O&M Quick
2A00
O&M Rating
20
Overall Index
2
Overall Quick
Overall Rating
68
Pipe schematic from manhole J 0155 to J 0156
MH: J 0155MH: J 0156upstream0 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - DEBRIS47.6 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start117.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start117.7 ft. MGO - General Observation - MAG COAT119.7 ft. MWM - Water Mark, 25 %of cross sectional area119.7 ft. MWL - Water Level, 5 %of cross sectional area119.7 ft. AMH - Downstream Manhole, Survey Begins - J 0155

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Deposits Settled Compacted,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    72.1 ft. - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Survey Abandoned - DEBRIS

    119.7 ft. - Survey Abandoned - DEBRIS

Observations (9)

DistanceCodeObservation
72.1DSC
2SSS
0MWM
119.7DSC
2MGOMAG COAT
119.7SSS
119.7MSADEBRIS
0MWL
0AMHJ 0155

Properties (7)

additional_info
630074021022202
custom_field_three
MAG COAT, SPALLING, DEBRIS
custom_field_two
5
customer
1
datetime
2022-02-11T02:31:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false