Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 17, 2022, 08:53 AM
  • J 0162_J 0161_02172022_011603.mp4

Date
02/17/2022
W/O
936261
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00055
PipeID
P11404
Time
12:53 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9738
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
RANCHO PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
44
Purpose
Routine Assessment
Project
WO_936261_TV05161_FEB2022
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
J 0162
Downstream MH
J 0161
Dir. of Survey
Downstream
Length Surveyed
912.6 ft.
Total Length
912.6 ft.
Structural Index
2
Structural Quick
513I
Structural Rating
511
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
511
Pipe schematic from manhole J 0162 to J 0161
MH: J 0162MH: J 0161downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 01627 ft. MGO - General Observation - MAG COAT7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start246.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish875 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: YES - POSSIBLY BROKEN REINFORCEMENT - CAMERA DID NOT STOP, NOR ZOOMED-IN.912.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish912.6 ft. AMH - Downstream Manhole, Survey Ends - J 0161

Observation photos (3)

  • General Observation - MAG COAT

    7 ft. - General Observation - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
875SRVPOSSIBLY BROKEN REINFORCEMENT - CAMERA DID NOT STOP, NOR ZOOMED-IN.
0MWL
246.1SAP
7MGOMAG COAT
7SAP
0MWM
912.6SSS
7SSS
912.6AMHJ 0161
0AMHJ 0162

Properties (7)

additional_info
630074021422001
custom_field_three
SPALLING, MAG COAT, AGGREGATE PRJECTING
custom_field_two
3
customer
1
datetime
2022-02-17T00:53:18-08:00
documentation
PRO PIPE
is_lateral_inspection
false