Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 16, 2022, 08:00 AM
  • J 0168_J 0167_02162022_002002.mp4

Date
02/16/2022
W/O
936261
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00055
PipeID
P11726
Time
12:00 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9737
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
SAN PEDRO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
44
Purpose
Routine Assessment
Project
WO_936261_TV05161_FEB2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
J 0168
Downstream MH
J 0167
Dir. of Survey
Downstream
Length Surveyed
574.7 ft.
Total Length
574.7 ft.
Structural Index
2
Structural Quick
2V00
Structural Rating
228
O&M Index
3
O&M Quick
3C00
O&M Rating
60
Overall Index
2
Overall Quick
Overall Rating
288
Pipe schematic from manhole J 0168 to J 0167
MH: J 0168MH: J 0167downstream0 ft. AMH - Upstream Manhole, Survey Begins - J 01680 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area3.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.2 ft. MGO - General Observation - MAG COAT167.6 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start268.3 ft. DSC - Deposits Settled Compacted, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish574.7 ft. AMH - Downstream Manhole, Survey Ends - J 0167574.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    3.2 ft. - General Observation - MAG COAT

  • Deposits Settled Compacted,  15 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    167.6 ft. - Deposits Settled Compacted, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0AMHJ 0168
0MWL
3.2SSS
574.7AMHJ 0167
0MWM
268.3DSC
3.2MGOMAG COAT
574.7SSS
167.6DSC

Properties (7)

additional_info
630074021522201
custom_field_three
SPALLING, MAG COAT
custom_field_two
3
customer
1
datetime
2022-02-16T00:00:50-08:00
documentation
PRO PIPE
is_lateral_inspection
false