Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2022, 10:10 AM
  • J 0156_J 0155_02112022_021923.mp4

Date
02/11/2022
W/O
936261
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00055
PipeID
P11396
Time
2:10 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9734
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
RANCHO PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
40
Purpose
Routine Assessment
Project
WO_936261_TV05161_FEB2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
J 0156
Downstream MH
J 0155
Dir. of Survey
Downstream
Length Surveyed
70 ft.
Total Length
70 ft.
Structural Index
2
Structural Quick
2B00
Structural Rating
28
O&M Index
2
O&M Quick
2700
O&M Rating
14
Overall Index
2
Overall Quick
Overall Rating
42
Pipe schematic from manhole J 0156 to J 0155
MH: J 0156MH: J 0155downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 01560 ft. MGO - General Observation - ACTIVE CONNECTION AT THE MH 9 O'CLOCK2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COAT35 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start70 ft. MSA - Survey Abandoned - DEBRIS70 ft. DSC - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish70 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Deposits Settled Compacted,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    35 ft. - Deposits Settled Compacted, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Survey Abandoned - DEBRIS

    70 ft. - Survey Abandoned - DEBRIS

Observations (10)

DistanceCodeObservation
0MWL
70MSADEBRIS
0MWM
0AMHJ 0156
35DSC
2SSS
70DSC
0MGOACTIVE CONNECTION AT THE MH 9 O'CLOCK
2MGOMAG COAT
70SSS

Properties (7)

additional_info
630074021022202
custom_field_three
MAG COAT, SPALLING, DEBRIS
custom_field_two
5
customer
1
datetime
2022-02-11T02:10:48-08:00
documentation
PRO PIPE
is_lateral_inspection
false