Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 24, 2022, 06:08 PM
  • J 0342_J 0341_02242022_102254.mp4

Date
02/24/2022
W/O
936478
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00059
PipeID
P11586
Time
10:08 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9908
Sewer Name
J JOINT OUTFALL J - UNIT 1G
City
PALOS VERDES ESTATES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_936478_TV05330_FEB2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
J 0342
Downstream MH
J 0341
Dir. of Survey
Downstream
Length Surveyed
44.6 ft.
Total Length
44.6 ft.
Structural Index
3
Structural Quick
443A
Structural Rating
49
O&M Index
2
O&M Quick
2800
O&M Rating
16
Overall Index
3
Overall Quick
Overall Rating
65
Pipe schematic from manhole J 0342 to J 0341
MH: J 0342MH: J 0341downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 03420 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - HIGH/FAST FLOW COMING FROM HILL0 ft. MGO - General Observation - CONN @ MH 5 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.8 ft. CM - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES14.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES26.2 ft. CC - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES27.2 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES27.2 ft. MGO - General Observation - MISSING PIPE 12 O'CLOCK29.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start42 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish42 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish42.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish44.6 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES44.6 ft. MSA - Survey Abandoned - CAMERA GOING UNDER WATER POSSIBLE SAG

Observation photos (7)

  • Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES

    9.8 ft. - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    14.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

    26.2 ft. - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

  • General Observation - MISSING PIPE 12 O'CLOCK

    27.2 ft. - General Observation - MISSING PIPE 12 O'CLOCK

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    29.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES

    44.6 ft. - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - CAMERA GOING UNDER WATER POSSIBLE SAG

    44.6 ft. - Survey Abandoned - CAMERA GOING UNDER WATER POSSIBLE SAG

Observations (18)

DistanceCodeObservation
42.9FM
0MWM
42DAGS
9.8CM
27.2H
0AMHJ 0342
0MWL
42CM
2DAGS
2CM
27.2MGOMISSING PIPE 12 O'CLOCK
0MGOHIGH/FAST FLOW COMING FROM HILL
0MGOCONN @ MH 5 O'CLOCK/ACTIVE
44.6FC
26.2CC
29.9FM
44.6MSACAMERA GOING UNDER WATER POSSIBLE SAG
14.4FM

Properties (7)

additional_info
630138022422062
custom_field_three
HOLE IN PIPE
custom_field_two
5
customer
1
datetime
2022-02-24T10:08:37-08:00
documentation
PROPIPE
is_lateral_inspection
false