Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 9, 2022, 09:14 AM
  • 32 1238_32 1237_03092022_025435.mp4

Date
03/09/2022
W/O
941332
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00832
PipeID
P19707
Time
1:14 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10002
Sewer Name
32 BOUQUET CANYON TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
07
Purpose
Routine Assessment
Project
WO_941332_TV32007_MAR2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
32 1238
Downstream MH
32 1237
Dir. of Survey
Downstream
Length Surveyed
403.3 ft.
Total Length
403.3 ft.
Structural Index
2
Structural Quick
3J2O
Structural Rating
319
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
319
Pipe schematic from manhole 32 1238 to 32 1237
MH: 32 1238MH: 32 1237downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 12380 ft. MWL - Water Level, 5 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start27.4 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES49.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"200.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"203.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"351.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"354 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"400.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish401 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish403.3 ft. AMH - Downstream Manhole, Survey Ends - 32 1237403.3 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE403.3 ft. MGO - General Observation - DATA STATES NRCP. MATERIAL IS VCP.

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    27.4 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
203.1TFC
400.8CM
403.3AMH32 1237
354TFC
403.3MGOCONN @ MH 3 O'CLOCK/ACTIVE
27.4CM
351.6TFC
0MWL
2CM
126.5TFC
403.3MGODATA STATES NRCP. MATERIAL IS VCP.
277.6TFC
200.3TFC
2SSS
49.2TFC
0AMH32 1238
401SSS
0MWL
123.5TFC

Properties (7)

additional_info
630138030822202
custom_field_three
SPALLING/CRACKS
custom_field_two
3
customer
1
datetime
2022-03-09T01:14:18-08:00
documentation
PRO PIPE
is_lateral_inspection
false