Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2022, 06:06 AM
  • 22 0469_22 0468_02092022_222409.mp4

Date
02/09/2022
W/O
936485
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00816
PipeID
P16807
Time
10:06 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9779
Sewer Name
22 LARK ELLEN TRUNK, SECTS 4,5,&6
City
AZUSA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_936485_TV22049_FEB2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0468
Downstream MH
22 0469
Dir. of Survey
Upstream
Length Surveyed
279.4 ft.
Total Length
279.4 ft.
Structural Index
3
Structural Quick
3J2C
Structural Rating
205
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
205
Pipe schematic from manhole 22 0468 to 22 0469
MH: 22 0468MH: 22 0469upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 04690 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish59.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"68.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"101.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish101.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start101.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start120.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"193.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"198.5 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 4"263.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"277.4 ft. MGO - General Observation - MAG COATING277.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start279.4 ft. MWM - Water Mark, 15 %of cross sectional area279.4 ft. MWL - Water Level, 5 %of cross sectional area279.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK279.4 ft. AMH - Downstream Manhole, Survey Begins - 22 0468

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    177.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    177.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
219.8TF
0MWM
277.3SAP
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
80.9TB
279.4AMH22 0469
177.8SAV
177.8SAP
0AMH22 0468
2MGOMAG COATING
159TF
277.3SSS
2SAV
86.2TF
279.4MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
177.8SSS
16.3TF
211.2TBA

Properties (7)

additional_info
630098020922201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-02-09T22:06:37-08:00
documentation
PROPIPE
is_lateral_inspection
false