Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2022, 07:08 AM
  • 22 0467_22 0466_02092022_232155.mp4

Date
02/09/2022
W/O
936485
Weather
Dry
Operator/Surveyor
J.BUENROSTRO
Sewer ID
Z00816
PipeID
P16805
Time
11:08 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9779
Sewer Name
22 LARK ELLEN TRUNK, SECTS 4,5,&6
City
AZUSA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_936485_TV22049_FEB2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
22 0467
Downstream MH
22 0466
Dir. of Survey
Downstream
Length Surveyed
279.3 ft.
Total Length
279.3 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
165
Pipe schematic from manhole 22 0467 to 22 0466
MH: 22 0467MH: 22 0466downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 04670 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - MAG COATING81.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"85.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"140.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"196.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"201.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"262.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"276.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish279.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK279.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0466

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0AMH22 0467
140.6TFC
262.8TF
2.6SAP
196.9TF
279.3MGOCONNECTION AT MH 9 O'CLOCK
201.1TF
85.2TF
0MWL
81.7TF
0MWM
2.6MGOMAG COATING
0MGOCONNECTION AT MH 9 O'CLOCK
279.3AMH22 0466
276.3SAP

Properties (7)

additional_info
630098020922201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-02-09T23:08:38-08:00
documentation
PROPIPE
is_lateral_inspection
false