Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2022, 10:10 AM
  • 01 0802_01 1375_02082022_021759.mp4

Date
02/08/2022
W/O
936489
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00197
PipeID
P21617
Time
2:10 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9725
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_936489_TV01264_FEB2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0802
Downstream MH
01 1375
Dir. of Survey
Downstream
Length Surveyed
28.9 ft.
Total Length
28.9 ft.
Structural Index
4
Structural Quick
5234
Structural Rating
22
O&M Index
2
O&M Quick
4125
O&M Rating
14
Overall Index
3
Overall Quick
Overall Rating
36
Pipe schematic from manhole 01 0802 to 01 1375
MH: 01 0802MH: 01 1375downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 08020 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES4.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish9 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Start17 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Finish17 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Start28.9 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish28.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish28.9 ft. AMH - Downstream Manhole, Survey Ends - 01 1375

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Broken, at 12 o'clock, within 8 inches of joint: YES, Start

    9 ft. - Broken, at 12 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    17 ft. - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMH01 0802
17B
28.9B
17B
2DAGS
9FL
9B
4CM
0MWM
28.9DAGS
4.1FL
0MWL
28.9AMH01 1375

Properties (7)

additional_info
630074020722202
custom_field_three
BROKEN PIPE
custom_field_two
1
customer
1
datetime
2022-02-08T02:10:22-08:00
documentation
PRO PIPE
is_lateral_inspection
false