Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 29, 2021, 08:05 AM
  • 05 0157_05 0156_12292021_002104.mp4

Date
12/29/2021
W/O
926973
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05449
Time
12:05 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9575
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_926973_TV05147_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
54 in.
Upstream MH
05 0157
Downstream MH
05 0156
Dir. of Survey
Downstream
Length Surveyed
329.4 ft.
Total Length
329.4 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
195
Pipe schematic from manhole 05 0157 to 05 0156
MH: 05 0157MH: 05 0156downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 01570 ft. MWM - Water Mark, 40 %of cross sectional area0.1 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAG COAT325.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0156

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWL
2.3SAV
2.3MGOMAG COAT
0.1MGOCONNECTION AT THE MH 9 OC'LOCK
329.4AMH05 0156
0AMH05 0157
0MWM
325.5SAV

Properties (7)

additional_info
630074122821202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-12-29T00:05:19-08:00
documentation
PROPIPE
is_lateral_inspection
false