Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2022, 03:16 PM
  • 05 0132A_05 0132_01252022_073139.mp4

Date
01/25/2022
W/O
926973
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05423
Time
7:16 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9583
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_926973_TV05147_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
42 in.
Upstream MH
05 0132
Downstream MH
05 0132A
Dir. of Survey
Upstream
Length Surveyed
212.6 ft.
Total Length
212.6 ft.
Structural Index
3
Structural Quick
3G2G
Structural Rating
210
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
212
Pipe schematic from manhole 05 0132 to 05 0132A
MH: 05 0132MH: 05 0132Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 0132A0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - MAP FOOTAGE WRONG0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK68.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO - SLUDGE210.6 ft. MGO - General Observation - MAG COATING THROUGHOUT210.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start210.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start212.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK212.6 ft. MWM - Water Mark, 15 %of cross sectional area212.6 ft. MWL - Water Level, 10 %of cross sectional area212.6 ft. AMH - Downstream Manhole, Survey Begins - 05 0132

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO - SLUDGE

    143.7 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO - SLUDGE

Observations (13)

DistanceCodeObservation
0MGOCONNECTION AT MH 3 O'CLOCK
212.6AMH05 0132A
0MWM
212.6SAV
212.6MGOMAP FOOTAGE WRONG
143.7DSZSLUDGE
0MWL
2MGOMAG COATING THROUGHOUT
2SAV
0AMH05 0132
212.6SSS
212.6MGOCONNECTION AT MH 3 O'CLOCK
2SSS

Properties (7)

additional_info
630098012522051
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-01-25T07:16:27-08:00
documentation
PROPIPE
is_lateral_inspection
false