Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2022, 03:53 PM
  • 05 0132_05 0131_01252022_080404.mp4

Date
01/25/2022
W/O
926973
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05422
Time
7:53 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9583
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
HAWTHRONE
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_926973_TV05147_DEC2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
42 in.
Upstream MH
05 0132
Downstream MH
05 0131
Dir. of Survey
Downstream
Length Surveyed
333.2 ft.
Total Length
333.2 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
197
Pipe schematic from manhole 05 0132 to 05 0131
MH: 05 0132MH: 05 0131downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 01320 ft. MWM - Water Mark, 10 %of cross sectional area2 ft. MGO - General Observation - MAG COATING THROUGHOUT8.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start186.8 ft. DAR - Deposits Attached Ragging, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES332.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish333.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0131333.2 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    8.4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Ragging, 10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES

    186.8 ft. - Deposits Attached Ragging, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
332.9SAP
2MGOMAG COATING THROUGHOUT
333.2AMH05 0131
0AMH05 0132
333.2MGOCONNECTION AT MH 9 O'CLOCK
186.8DAR
0MWM
8.4SAP

Properties (7)

additional_info
630098012522051
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-01-25T07:53:37-08:00
documentation
PROPIPE
is_lateral_inspection
false