Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2022, 06:56 AM
  • 08 0028_08 0557_02032022_230417.mp4

Date
02/03/2022
W/O
931501
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00016
PipeID
P00030
Time
10:56 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9862
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
08 0557
Downstream MH
08 0028
Dir. of Survey
Upstream
Length Surveyed
59.2 ft.
Total Length
311.8 ft.
Structural Index
2
Structural Quick
2A00
Structural Rating
22
O&M Index
2
O&M Quick
312A
O&M Rating
25
Overall Index
2
Overall Quick
Overall Rating
47
Pipe schematic from manhole 08 0557 to 08 0028
MH: 08 0557MH: 08 0028upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish0 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - DEBRIS0 ft. MSA - Survey Abandoned - DUE TO DEBRIS. REVERSAL COMPLETE.0.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish4.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"57.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start59.2 ft. MWL - Water Level, 40 %of cross sectional area59.2 ft. MWM - Water Mark, 45 %of cross sectional area59.2 ft. MGO - General Observation - ROACHES @ MH59.2 ft. AMH - Downstream Manhole, Survey Begins - 08 0557

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
59.2DAGS
0MWL
59.2DSZDEBRIS
0MWM
0MGOROACHES @ MH
0AMH08 0557
54.4TFC
2SSS
2DAGS
59SSS
59.2MSADUE TO DEBRIS. REVERSAL COMPLETE.

Properties (7)

additional_info
630138020322201
custom_field_three
MULTIPLE CRACKS/DEBRIS
custom_field_two
2
customer
1
datetime
2022-02-03T22:56:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false