Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2022, 06:58 AM
  • 08 0061_08 0060_02012022_231548.mp4

Date
02/01/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00063
Time
10:58 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9722
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
08 0061
Downstream MH
08 0060
Dir. of Survey
Downstream
Length Surveyed
296.6 ft.
Total Length
296.6 ft.
Structural Index
2
Structural Quick
3J2K
Structural Rating
288
O&M Index
2
O&M Quick
2K1D
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
428
Pipe schematic from manhole 08 0061 to 08 0060
MH: 08 0061MH: 08 0060downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00610 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.2 ft. CS - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES9.2 ft. CS - Crack Spiral, from 11 to 04 o'clock, within 8 inches of joint: YES18.1 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES21.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36.6 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES37.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN88.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"132.2 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES136.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN146.5 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES152.5 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES155.7 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start187.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"258.1 ft. RFJ - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish294 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish294 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish296 ft. MGO - General Observation - ROACHES @ MH296.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0060296.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE296.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (9)

  • Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

    3.2 ft. - Crack Spiral, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 11 to 04 o'clock, within 8 inches of joint: YES

    9.2 ft. - Crack Spiral, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    18.1 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES

    36.6 ft. - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

    132.2 ft. - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

    146.5 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

    152.5 ft. - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    155.7 ft. - Roots Fine Joint, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (27)

DistanceCodeObservation
37.9TFOPEN
296.6AMH08 0060
294DAGS
36.6RFJ
0MWL
296MGOROACHES @ MH
88.7TFC
0MWM
258.1RFJ
18.1CM
296.6MGOCONN @ MH 9 O'CLOCK/ACTIVE
187.2TFC
2DAGS
0AMH08 0061
152.5RFJ
294SSS
2SSS
296.6MGOCONN @ MH 3 O'CLOCK/ACTIVE
3.2CS
21.4CM
146.5RFJ
9.2CS
132.2RFJ
294.7CM
136.5TFOPEN
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
155.7RFJ

Properties (7)

additional_info
630074020122201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-01T22:58:08-08:00
documentation
PRO PIPE
is_lateral_inspection
false