Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2022, 09:01 AM
  • 08 0060_08 0059_02022022_011341.mp4

Date
02/02/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00062
Time
1:01 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9722
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
08 0059
Downstream MH
08 0060
Dir. of Survey
Upstream
Length Surveyed
283.5 ft.
Total Length
283.5 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
280
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
392
Pipe schematic from manhole 08 0059 to 08 0060
MH: 08 0059MH: 08 0060upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 00600 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.5 ft. MGO - General Observation - ROACHES @ MH2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish114.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"171.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"232 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"281.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start281.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start281.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start283.5 ft. AMH - Downstream Manhole, Survey Begins - 08 0059283.5 ft. MGO - General Observation - ROACHES @ MH283.5 ft. MWL - Water Level, 25 %of cross sectional area283.5 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
51.5TFC
283.5AMH08 0060
2SSS
283.5MGOCONN @ MH 9 O'CLOCK/ACTIVE
283.5MGOCONN @ MH 3 O'CLOCK/ACTIVE
2DAGS
281DAGS
2CM
0AMH08 0059
111.6TFC
281SSS
283.5CM
0MGOROACHES @ MH
0MWL
283MGOROACHES @ MH
169.2TFC
0MWM

Properties (7)

additional_info
630074020122201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-02T01:01:10-08:00
documentation
PRO PIPE
is_lateral_inspection
false