Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2022, 09:45 AM
  • 08 0057_08 0056_02022022_020154.mp4

Date
02/02/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00059
Time
1:45 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9722
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
08 0057
Downstream MH
08 0056
Dir. of Survey
Downstream
Length Surveyed
336.9 ft.
Total Length
336.9 ft.
Structural Index
3
Structural Quick
3L21
Structural Rating
203
O&M Index
2
O&M Quick
413F
O&M Rating
259
Overall Index
2
Overall Quick
Overall Rating
462
Pipe schematic from manhole 08 0057 to 08 0056
MH: 08 0057MH: 08 0056downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED0 ft. MGO - General Observation - ROACHES @ MH0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 08 00570 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start13.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES48.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start75.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN75.1 ft. RFL - Roots Fine Lateral, from 08 to 04 o'clock121.6 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YESR, Start121.6 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish135.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"195.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"254.7 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4", 6" - 80% ROOTS-LATERAL/OPEN254.7 ft. RBL - Roots Ball Lateral, from 12 to 12 o'clock, 90 %254.7 ft. RMC - Roots Medium Connection, from 08 to 10 o'clock, 15 %, within 8 inches of joint: NO292.4 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YESR, Finish315.3 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN334 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish334.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish336 ft. MGO - General Observation - ROACHES @ MH336.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE336.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0056

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    13.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    48.7 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Lateral, from 08 to 04 o'clock

    75.1 ft. - Roots Fine Lateral, from 08 to 04 o'clock

  • Roots Medium Joint, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YESR, Start

    121.6 ft. - Roots Medium Joint, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YESR, Start

  • Roots Ball Lateral, from 12 to 12 o'clock, 90 %

    254.7 ft. - Roots Ball Lateral, from 12 to 12 o'clock, 90 %

  • Roots Medium Connection, from 08 to 10 o'clock, 15 %, within 8 inches of joint: NO

    254.7 ft. - Roots Medium Connection, from 08 to 10 o'clock, 15 %, within 8 inches of joint: NO

Observations (26)

DistanceCodeObservation
121.6RMJ
334.7CM
336MGOROACHES @ MH
336.9MGOCONN @ MH 3 O'CLOCK/ACTIVE
2CM
75.1TFOPEN
254.7TFD80% ROOTS-LATERAL/OPEN
0MGOCONN @ MH 3 O'CLOCK/CAPPED
0MGOROACHES @ MH
135.5TFC
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
75.1RFL
195.7TFC
315.3TFOPEN
292.4RMJ
254.7RBL
0AMH08 0057
121.6RFJ
13.1CL
48.7RFJ
336.9AMH08 0056
334DAGS
2DAGS
254.7RMC
0MWL
0MWM

Properties (7)

additional_info
630074020122201
custom_field_three
CRACKS, ROOTS
custom_field_two
3
customer
1
datetime
2022-02-02T01:45:10-08:00
documentation
PRO PIPE
is_lateral_inspection
false