Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2022, 08:19 AM
  • 08 0063_08 0062_02022022_002727.mp4

Date
02/02/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00065
Time
12:19 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9722
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
08 0063
Downstream MH
08 0062
Dir. of Survey
Downstream
Length Surveyed
125.6 ft.
Total Length
125.6 ft.
Structural Index
3
Structural Quick
3D2D
Structural Rating
120
O&M Index
2
O&M Quick
2D00
O&M Rating
48
Overall Index
2
Overall Quick
Overall Rating
168
Pipe schematic from manhole 08 0063 to 08 0062
MH: 08 0063MH: 08 0062downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 00630 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start70.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"123 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish123 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish125.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish125.6 ft. MSA - Survey Abandoned - COMPLETED REVERSAL

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Survey Abandoned - COMPLETED REVERSAL

    125.6 ft. - Survey Abandoned - COMPLETED REVERSAL

Observations (14)

DistanceCodeObservation
0AMH08 0063
0MWM
2DAGS
123DAGS
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
0MWL
0MGOROACHES @ MH
5.6CM
123SSS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
125.6CM
2SSS
125.6MSACOMPLETED REVERSAL
70.9TFC

Properties (7)

additional_info
630074020122201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-02T00:19:33-08:00
documentation
PRO PIPE
is_lateral_inspection
false