Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2022, 09:02 AM
  • 08 0083_08 0082_01252022_011823.mp4

Date
01/25/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00111
Time
1:02 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9712
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
12 in.
Upstream MH
08 0083
Downstream MH
08 0082
Dir. of Survey
Downstream
Length Surveyed
245.4 ft.
Total Length
245.4 ft.
Structural Index
2
Structural Quick
3H2I
Structural Rating
237
O&M Index
2
O&M Quick
2H00
O&M Rating
94
Overall Index
2
Overall Quick
Overall Rating
331
Pipe schematic from manhole 08 0083 to 08 0082
MH: 08 0083MH: 08 0082downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 00830 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.7 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES5.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"61.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"109.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"147.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN161.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"210.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"242.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish242.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish243 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish245.4 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN245.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0082

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    5.7 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    5.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

    147.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

Observations (19)

DistanceCodeObservation
2CM
5.7CM
243SSS
245.4MGOCONN @ MH 3 O'CLOCK/OPEN
9.7TFC
242.4CM
245.4AMH08 0082
0AMH08 0083
109.8TFC
242.4DAGS
0MWM
210.3TFC
0MWL
147.9TBOPEN
5.7DAGS
2SSS
161.7TFC
61.2TFC
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN

Properties (7)

additional_info
630098012422201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-01-25T01:02:57-08:00
documentation
PRO PIPE
is_lateral_inspection
false