Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2022, 08:05 AM
  • 08 0067_08 0066_02012022_003701.mp4

Date
02/01/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00069
Time
12:05 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9719
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0066
Downstream MH
08 0067
Dir. of Survey
Upstream
Length Surveyed
250.4 ft.
Total Length
250.4 ft.
Structural Index
2
Structural Quick
3I2I
Structural Rating
242
O&M Index
2
O&M Quick
2I18
O&M Rating
106
Overall Index
2
Overall Quick
Overall Rating
348
Pipe schematic from manhole 08 0066 to 08 0067
MH: 08 0066MH: 08 0067upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 00670 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish28.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36.1 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES38.4 ft. RFJ - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES49.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"99.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN151.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"200.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"240.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start244.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"248.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start248.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start250.4 ft. MWM - Water Mark, 20 %of cross sectional area250.4 ft. MGO - General Observation - ROACHES @ MH250.4 ft. AMH - Downstream Manhole, Survey Begins - 08 0066250.4 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

    212 ft. - Roots Fine Joint, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

    214.3 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    221.5 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
248SSS
0MWM
0MGOROACHES @ MH
10.1CM
250.4AMH08 0067
250.4RFJ
50.3TFC
212RFJ
248DAGS
214.3RFJ
151.2TFOPEN
2SSS
250.4CM
2DAGS
221.5RFJ
98.6TFC
6.1TFC
0AMH08 0066
201.1TFC
0MWL

Properties (7)

additional_info
630074013122201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-01T00:05:30-08:00
documentation
PRO PIPE
is_lateral_inspection
false