Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2022, 07:07 AM
  • 08 0065_08 0064_01312022_234926.mp4

Date
01/31/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00067
Time
11:07 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9719
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
08 0065
Downstream MH
08 0064
Dir. of Survey
Downstream
Length Surveyed
330 ft.
Total Length
330 ft.
Structural Index
3
Structural Quick
514L
Structural Rating
391
O&M Index
2
O&M Quick
2L12
O&M Rating
132
Overall Index
3
Overall Quick
Overall Rating
523
Pipe schematic from manhole 08 0065 to 08 0064
MH: 08 0065MH: 08 0064downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 00650 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES3.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"38.8 ft. RFJ - Roots Fine Joint, from 11 to 12 o'clock, within 8 inches of joint: YES42 ft. RFJ - Roots Fine Joint, at 11 o'clock, within 8 inches of joint: YES70.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN121.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN173.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"212.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"215.8 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OPEN273.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"321.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN325.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE330 ft. AMH - Downstream Manhole, Survey Ends - 08 0064330 ft. MGO - General Observation - ROACHES @ MH

Observation photos (4)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 11 to 12 o'clock, within 8 inches of joint: YES

    38.8 ft. - Roots Fine Joint, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 11 o'clock, within 8 inches of joint: YES

    42 ft. - Roots Fine Joint, at 11 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    215.8 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

Observations (25)

DistanceCodeObservation
330MGOCONN @ MH 3 O'CLOCK/ACTIVE
0AMH08 0065
215.8TBOPEN
273.4TFC
19.6TFC
3B
2SSS
38.8RFJ
2DAGS
0MWL
3.1FM
121.6TFOPEN
330AMH08 0064
42RFJ
212.5TFC
328DAGS
325.4FM
0MWM
328SSS
330MGOROACHES @ MH
321.2TFOPEN
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
173.9TFC
70.6TFOPEN
0MGOROACHES @ MH

Properties (7)

additional_info
630074013122201
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2022-01-31T23:07:38-08:00
documentation
PRO PIPE
is_lateral_inspection
false