Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2022, 07:03 AM
  • 08 0091_08 0090_01252022_232124.mp4

Date
01/25/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00119
Time
11:03 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9714
Sewer Name
08 MAIN STREET TRUNK
City
WILLOWBROOK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
01
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
8 in.
Upstream MH
08 0091
Downstream MH
08 0090
Dir. of Survey
Downstream
Length Surveyed
369.5 ft.
Total Length
369.5 ft.
Structural Index
3
Structural Quick
3M2N
Structural Rating
362
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
514
Pipe schematic from manhole 08 0091 to 08 0090
MH: 08 0091MH: 08 0090downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00912 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.1 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"121.3 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"218.6 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"323.1 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN367 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish367.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish367.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish369 ft. MGO - General Observation - ROACHES @ MH369.5 ft. AMH - Downstream Manhole, Survey Ends - 08 0090

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    18.1 ft. - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    121.3 ft. - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"

    218.6 ft. - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

    323.1 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 8" - OPEN

Observations (15)

DistanceCodeObservation
369MGOROACHES @ MH
2SSS
0MWL
18.1TBC
218.6TBC
0MWM
367SSS
323.1TBOPEN
367.4CM
121.3TBC
369.5AMH08 0090
2.1DAGS
367.4DAGS
9CM
0AMH08 0091

Properties (7)

additional_info
630074012522201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-01-25T23:03:35-08:00
documentation
PRO PIPE
is_lateral_inspection
false