Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2022, 09:36 AM
  • 08 0085_08 0084_01262022_015622.mp4

Date
01/26/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00113
Time
1:36 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9714
Sewer Name
08 MAIN STREET TRUNK
City
WILLOWBROOK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0085
Downstream MH
08 0084
Dir. of Survey
Downstream
Length Surveyed
410.7 ft.
Total Length
410.7 ft.
Structural Index
2
Structural Quick
322O
Structural Rating
168
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
176
Pipe schematic from manhole 08 0085 to 08 0084
MH: 08 0085MH: 08 0084downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN0 ft. AMH - Upstream Manhole, Survey Begins - 08 00850 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.2 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"62.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"112.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"161.8 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8" - OPEN210.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"262.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"311.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"360.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8" - OPEN407.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish407.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish408 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish410 ft. MGO - General Observation - ROACHES @ MH410.7 ft. AMH - Downstream Manhole, Survey Ends - 08 0084410.7 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/OPEN410.7 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"

    16.2 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"

    62.4 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"

Observations (23)

DistanceCodeObservation
0MWL
311.1TFC
410.7AMH08 0084
408SSS
62.4TBC
407.7CM
262.3TFC
410.7MGOCONN @ MH 3 O'CLOCK/OPEN
0MGOROACHES @ MH
0MGOCONN @ MH 3 O'CLOCK/OPEN
2.6DAGS
360.4TFOPEN
407.7DAGS
112.9TFC
410.7MGOCONN @ MH 9 O'CLOCK/CAPPED
161.8TFOPEN
0AMH08 0085
210.8TFC
16.2TBC
5.3CM
410MGOROACHES @ MH
0MWM
2SSS

Properties (7)

additional_info
630074012522201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-01-26T01:36:35-08:00
documentation
PRO PIPE
is_lateral_inspection
false