Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2022, 07:24 AM
  • 08 0046_08 0045_02022022_233747.mp4

Date
02/02/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00048
Time
11:24 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9723
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
21 in.
Upstream MH
08 0046
Downstream MH
08 0045
Dir. of Survey
Downstream
Length Surveyed
311 ft.
Total Length
311 ft.
Structural Index
2
Structural Quick
3H2K
Structural Rating
263
O&M Index
2
O&M Quick
2W00
O&M Rating
242
Overall Index
2
Overall Quick
Overall Rating
505
Pipe schematic from manhole 08 0046 to 08 0045
MH: 08 0046MH: 08 0045downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 00460 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16.7 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start38.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"45.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES81.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.6 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 4", 6" - 65% GREASE-LATERAL/OPEN140.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"191.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - 65% GREASE-LATERAL/OPEN239.4 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"290.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN309 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish309 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311 ft. MGO - General Observation - ROIACHES @ MH311 ft. AMH - Downstream Manhole, Survey Ends - 08 0045311 ft. DSC - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish311 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Settled Compacted,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    16.7 ft. - Deposits Settled Compacted, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    45.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    81.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
311MGOROIACHES @ MH
0AMH08 0046
0MWL
311AMH08 0045
89.6TFD65% GREASE-LATERAL/OPEN
16.7DSC
2SSS
2DAGS
0MGOROACHES @ MH
311DSC
38.5TFC
311CM
290.5TFOPEN
191.5TF65% GREASE-LATERAL/OPEN
45.2CM
140.7TFC
81.7CM
0MWM
239.4TFC
309DAGS
309SSS

Properties (7)

additional_info
630074020222201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-02T23:24:48-08:00
documentation
PRO PIPE
is_lateral_inspection
false