Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2022, 08:35 AM
  • 08 0044_08 0043_02032022_004953.mp4

Date
02/03/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00046
Time
12:35 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9723
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
21 in.
Upstream MH
08 0043
Downstream MH
08 0044
Dir. of Survey
Upstream
Length Surveyed
307.6 ft.
Total Length
307.6 ft.
Structural Index
2
Structural Quick
322K
Structural Rating
128
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
252
Pipe schematic from manhole 08 0043 to 08 0044
MH: 08 0043MH: 08 0044upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 00442.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish7.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES17.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"19 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES67.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"68.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"118.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"165.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES167.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"217.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"267.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN305.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start305.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start307.6 ft. MWL - Water Level, 25 %of cross sectional area307.6 ft. MGO - General Observation - ROACHES @ MH307.6 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE307.6 ft. MWM - Water Mark, 30 %of cross sectional area307.6 ft. AMH - Downstream Manhole, Survey Begins - 08 0043

Observation photos (4)

  • Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock,  , within 8 inches of joint: YES

    141.9 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"

    240 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    288.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    300 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
239.2TFC
240TBA
0MWL
305DAGS
305SSS
300CM
141.9DAGS
288.6CM
2SSS
188.8TFC
2DAGS
290.1TFC
140.1TFA
0MGOROACHES @ MH
90.4TFC
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
40TFOPEN
0MWM
307.6AMH08 0044
0AMH08 0043

Properties (7)

additional_info
630074020222201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-03T00:35:15-08:00
documentation
PRO PIPE
is_lateral_inspection
false