Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2022, 08:19 AM
  • 08 0043_08 0042_02032022_003418.mp4

Date
02/03/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00045
Time
12:19 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9723
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
21 in.
Upstream MH
08 0042
Downstream MH
08 0043
Dir. of Survey
Upstream
Length Surveyed
307.3 ft.
Total Length
307.3 ft.
Structural Index
2
Structural Quick
322K
Structural Rating
130
O&M Index
2
O&M Quick
2K00
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
252
Pipe schematic from manhole 08 0042 to 08 0043
MH: 08 0042MH: 08 0043upstream0 ft. AMH - Upstream Manhole, Survey Ends - 08 00430.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE2.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish11.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"22.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES62.9 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"64.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES89.2 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN110.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN162 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN212.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"258.8 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES263.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4", 6"305.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start305.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start307.3 ft. MWM - Water Mark, 30 %of cross sectional area307.3 ft. MWL - Water Level, 25 %of cross sectional area307.3 ft. MGO - General Observation - ROACHES @ MH307.3 ft. AMH - Downstream Manhole, Survey Begins - 08 0042

Observation photos (4)

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    48.5 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

    218.1 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    243.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    285 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
305SSS
295.6TFC
48.5CL
0MWM
2SSS
0MWL
0MGOROACHES @ MH
2DAGS
196.5TFOPEN
305DAGS
243.2CM
244.4TFC
307.2MGOCONN @ MH 9 O'CLOCK/ACTIVE
145.3TFOPEN
94.5TFC
285CM
307.3AMH08 0043
43.8TFC
218.1TBOPEN
0AMH08 0042

Properties (7)

additional_info
630074020222201
custom_field_three
SPALLING/CRACKS
custom_field_two
3
customer
1
datetime
2022-02-03T00:19:12-08:00
documentation
PRO PIPE
is_lateral_inspection
false