Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2022, 10:23 AM
  • 08 0035_08 0034_02032022_024225.mp4

Date
02/03/2022
W/O
931501
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00016
PipeID
P00037
Time
2:23 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9723
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_931501_TV08116_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
08 0035
Downstream MH
08 0034
Dir. of Survey
Downstream
Length Surveyed
323.9 ft.
Total Length
323.9 ft.
Structural Index
2
Structural Quick
332L
Structural Rating
139
O&M Index
2
O&M Quick
3123
O&M Rating
9
Overall Index
2
Overall Quick
Overall Rating
148
Pipe schematic from manhole 08 0035 to 08 0034
MH: 08 0035MH: 08 0034downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 00350 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start11.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN62.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"111.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"161 ft. RMC - Roots Medium Connection, at 12 o'clock, 15 %, within 8 inches of joint: YES163.9 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6" - 70% ROOTS/ACTIVE210.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"227.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish255.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES259.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN267.4 ft. CM - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES311.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"321 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish323 ft. MGO - General Observation - ROACHES @ MH323.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE323.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0034

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Medium Connection, at 12 o'clock, 15 %, within 8 inches of joint: YES

    161 ft. - Roots Medium Connection, at 12 o'clock, 15 %, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    255.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES

    267.4 ft. - Crack Multiple, from 12 to 01 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
2SSS
0AMH08 0035
311.5TFC
2.1DAGS
0MWL
321.9DAGS
321SSS
161RMC
62.3TFC
323.9MGOCONN @ MH 3 O'CLOCK/ACTIVE
210.3TFC
2CM
323MGOROACHES @ MH
11.1TFOPEN
0MWM
111.3TFC
323.9AMH08 0034
259.5TFOPEN
163.9TFD70% ROOTS/ACTIVE
267.4CM
255.8CL
227.3CM

Properties (7)

additional_info
630074020222201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-03T02:23:36-08:00
documentation
PRO PIPE
is_lateral_inspection
false