Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 9, 2022, 09:26 AM
  • 20 0267_20 0196_02092022_013144.mp4

Date
02/09/2022
W/O
936488
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00739
PipeID
P19121
Time
1:26 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9867
Sewer Name
20 OUTFALL TRUNK
City
PALMDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_936488_TV20060_FEB2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
20 0196
Downstream MH
20 0267
Dir. of Survey
Upstream
Length Surveyed
29.8 ft.
Total Length
29.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 20 0196 to 20 0267
MH: 20 0196MH: 20 0267upstream0 ft. AMH - Upstream Manhole, Survey Ends - 20 02670 ft. MGO - General Observation - STOP LOG AT MOUTH OF PIPE.0.5 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish27.8 ft. SAP - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start29.8 ft. MWL - Water Level, 5 %of cross sectional area29.8 ft. AMH - Downstream Manhole, Survey Begins - 20 0196

Observation photos (2)

  • Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • General Observation - STOP LOG AT MOUTH OF PIPE.

    29.8 ft. - General Observation - STOP LOG AT MOUTH OF PIPE.

Observations (6)

DistanceCodeObservation
29.8AMH20 0267
0MWL
29.3SAP
0AMH20 0196
2SAP
29.8MGOSTOP LOG AT MOUTH OF PIPE.

Properties (7)

additional_info
630138020822201
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2022-02-09T01:26:05-08:00
documentation
PRO PIPE
is_lateral_inspection
false