Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2022, 08:52 AM
  • 01 1127_01 1126_02082022_011034.mp4

Date
02/08/2022
W/O
936473
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00210
PipeID
P01979
Time
12:52 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9724
Sewer Name
01 HUNTINGTON PARK TRUNK
City
CUDAHY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_936473_TV01246_FEB2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
01 1127
Downstream MH
01 1126
Dir. of Survey
Downstream
Length Surveyed
288.1 ft.
Total Length
288.1 ft.
Structural Index
3
Structural Quick
3G21
Structural Rating
125
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
125
Pipe schematic from manhole 01 1127 to 01 1126
MH: 01 1127MH: 01 1126downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11270 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK4.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES8.5 ft. CS - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES19.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"26.7 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES71.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"74.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"95.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start112.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"122.9 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"154.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"163.9 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"189.8 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"199.9 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: YES, 6"246.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"256.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6"284.7 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"288.1 ft. AMH - Downstream Manhole, Survey Ends - 01 1126288.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

    8.5 ft. - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

    19.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6"

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    26.7 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    95.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
19.7TB
0MWM
95.5CM
288.1AMH01 1126
122.9TF
246.3TF
0MWL
0AMH01 1127
154.4TFA
189.8TFA
284.7TF
112.8TF
288.1CM
0MGOCONNECTION AT THE MH 3 OC'LOCK
163.9TF
8.5CS
199.9TFA
74.6TF
4.1CM
256.6TF
0MGOCONNECTION AT THE MH 9 OC'LOCK
26.7CM
71.8TF

Properties (7)

additional_info
630074020722201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-08T00:52:59-08:00
documentation
PRO PIPE
is_lateral_inspection
false