Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2022, 07:59 AM
  • 01 1516_01 1084_02082022_001307.mp4

Date
02/07/2022
W/O
936473
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00210
PipeID
P01934
Time
11:59 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9724
Sewer Name
01 HUNTINGTON PARK TRUNK
City
CUDAHY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_936473_TV01246_FEB2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
18 in.
Upstream MH
01 1516
Downstream MH
01 1084
Dir. of Survey
Downstream
Length Surveyed
370.8 ft.
Total Length
370.8 ft.
Structural Index
3
Structural Quick
3M21
Structural Rating
215
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
217
Pipe schematic from manhole 01 1516 to 01 1084
MH: 01 1516MH: 01 1084downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 15160 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: YES4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES7.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start362 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish370.8 ft. AMH - Downstream Manhole, Survey Ends - 01 1084370.8 ft. MGO - General Observation - MOBILE MMS FOOTAGE - 371.07'.

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, at 08 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0AMH01 1516
0MWM
0MWL
7.1CM
362CM
2DAGS
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MGOCONNECTION AT THE MH 3 OC'LOCK
4CL
370.8AMH01 1084
370.8MGOMOBILE MMS FOOTAGE - 371.07'.

Properties (7)

additional_info
630074020722201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-02-07T23:59:17-08:00
documentation
PRO PIPE
is_lateral_inspection
false