Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2022, 07:35 PM
  • 15 0815_15 0814_3222022_123847.mp4

Date
03/22/2022
W/O
947360
Weather
Dry
Operator/Surveyor
BRAR
Sewer ID
Z00593
PipeID
P13016
Time
12:35 PM
Certificate
SEE REMARKS
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3045R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20220322SB_AR_SI_MD_TR_SEC_2_5
Material
NRCP
Shape
Circular
Height
9.399999618530273 in.
Upstream MH
15 0815
Downstream MH
15 0814
Dir. of Survey
Downstream
Length Surveyed
343.5 ft.
Total Length
343.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 15 0815 to 15 0814
MH: 15 0815MH: 15 0814downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 08150 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area - LINED PIPE12.5 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - 90% ROOTS IN LATERAL CONECTTION139.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"174.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"259.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"282.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"339 ft. MGO - General Observation - cAPPED CONNECTION AT 9 O'CLOCK340.4 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O'CLOCK341.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - THROUGHOUT REACH343.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0814, 101 PM

Observation photos (4)

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - 90% ROOTS IN LATERAL CONECTTION

    12.5 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 4" - 90% ROOTS IN LATERAL CONECTTION

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    139.7 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    174.6 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • General Observation - cAPPED CONNECTION AT 9 O'CLOCK

    339 ft. - General Observation - cAPPED CONNECTION AT 9 O'CLOCK

Observations (12)

DistanceCodeObservation
0AMH15 0815
343.5AMH15 0814, 101 PM
341.7DAGSTHROUGHOUT REACH
339MGOcAPPED CONNECTION AT 9 O'CLOCK
282.3TF
259.7TF
0MWM
340.4MGOCAPPED CONNECTION AT 3 O'CLOCK
139.7TF
174.6TFA
0MWLLINED PIPE
12.5TFD90% ROOTS IN LATERAL CONECTTION

Properties (8)

additional_info
U-0618-0703002249
custom_field_three
LINED PIPE, GREASE
custom_field_two
4
customer
LACSD
datetime
2022-03-22T12:35:39-07:00
documentation
BRAR, SHADLER, RAMIREJ
is_lateral_inspection
false
lining
PVCP