Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 11, 2022, 07:20 AM
  • 05 0723_05 0722_02102022_233934.mp4

Date
02/10/2022
W/O
936484
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00521
PipeID
P05946
Time
11:20 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9733
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_936484_TV05333_FEB2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0723
Downstream MH
05 0722
Dir. of Survey
Downstream
Length Surveyed
310 ft.
Total Length
310 ft.
Structural Index
4
Structural Quick
4K31
Structural Rating
243
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
243
Pipe schematic from manhole 05 0723 to 05 0722
MH: 05 0723MH: 05 0722downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 07237.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES8.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start44.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"92.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"143.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"192.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"246 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"294.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"310 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish310 ft. AMH - Downstream Manhole, Survey Ends - 05 0722

Observation photos (2)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    7.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
192.3TF
7.1FL
246TF
92.1TF
0MWL
8.7FM
0MWM
294.4TF
143.7TF
0AMH05 0723
44.3TF
310FM
310AMH05 0722

Properties (7)

additional_info
630074021022201
custom_field_three
CRACKS, FRACTURES
custom_field_two
2
customer
1
datetime
2022-02-10T23:20:07-08:00
documentation
PRO PIPE
is_lateral_inspection
false