Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2022, 11:06 AM
  • 03 0388_03 MARINA_02032022_031350.mp4

Date
02/03/2022
W/O
931714
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00371
PipeID
P05285
Time
3:06 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9773
Sewer Name
03 MARINA TRUNK, SECTION 2
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_931714_TV03135_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
36 in.
Upstream MH
03 0388
Downstream MH
03 MARINA
Dir. of Survey
Downstream
Length Surveyed
5.1 ft.
Total Length
5.1 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 03 0388 to 03 MARINA
MH: 03 0388MH: 03 MARINAdownstream0 ft. AMH - Upstream Manhole, Survey Begins - 03 03880 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES4.4 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES4.4 ft. MGO - General Observation - JOINT OFFSET4.4 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES5.1 ft. AEP - End of Pipe - 03 MARINA

Observation photos (3)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    2 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    4.4 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    4.4 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0AMH03 0388
5.1AEP03 MARINA
2CL
0MWM
0MWL
4.4FL
4.4MGOJOINT OFFSET
4.4FS

Properties (7)

additional_info
630098020222203
custom_field_three
FRACTURES
custom_field_two
2
customer
1
datetime
2022-02-03T03:06:17-08:00
documentation
PROPIPE
is_lateral_inspection
false