Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 1, 2022, 06:06 AM
  • 08 0031_08 0030_01312022_223308.mp4

Date
01/31/2022
W/O
931877
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00016
PipeID
P00033
Time
10:06 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9854
Sewer Name
08 MAIN STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_931877_TV08115_JAN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
08 0031
Downstream MH
08 0030
Dir. of Survey
Downstream
Length Surveyed
261.7 ft.
Total Length
261.7 ft.
Structural Index
3
Structural Quick
5132
Structural Rating
13
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 08 0031 to 08 0030
MH: 08 0031MH: 08 0030downstream0 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 00310 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.9 ft. B - Broken, from 11 to 06 o'clock, within 8 inches of joint: YES8.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"8.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES52.4 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS54.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"107.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"133.9 ft. MWL - Water Level, 25 %of cross sectional area156.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"205.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES206.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"207.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start258.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"261.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish261.5 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - DEBRIS261.5 ft. MSA - Survey Abandoned - DUE TO DEBRIS.261.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish261.7 ft. MWL - Water Level, 40 %of cross sectional area

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Broken, from 11 to 06 o'clock, within 8 inches of joint: YES

    7.9 ft. - Broken, from 11 to 06 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    8.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    205.8 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    207.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
207.9CM
258.5TFA
52.4DSZDEBRIS
205.8FL
261.5DAGS
8.8TFC
2DAGS
156.8TFC
0MGOCOCKROACHES IN MH
0MWL
206.4TFC
0AMH08 0031
7.9B
0MWM
107.9TFC
261.7MWL
8.8CL
133.9MWL
261.5DSZDEBRIS
54.9TFC
261.5MSADUE TO DEBRIS.
261.5CM

Properties (7)

additional_info
630138013122201
custom_field_three
ABANDONED DUE TO DEBRIS - NOTE: BROKEN PIPE -
custom_field_two
5
customer
1
datetime
2022-01-31T22:06:50-08:00
documentation
PRO PIPE
is_lateral_inspection
false