Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2022, 08:44 AM
  • 05 0292_05 0291_3172022_014857.mp4

Date
03/17/2022
W/O
0936513
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00498
PipeID
P05500
Time
1:44 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3038
Sewer Name
05 OAK STREET-CENTER AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20220316MDM_OAK_STREET_CENTER_AVENUE_TRUNK
Material
NRCP
Shape
Circular
Height
22 in.
Upstream MH
05 0292
Downstream MH
05 0291
Dir. of Survey
Downstream
Length Surveyed
333.9 ft.
Total Length
333.9 ft.
Structural Index
3
Structural Quick
4123
Structural Rating
10
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole 05 0292 to 05 0291
MH: 05 0292MH: 05 0291downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:45AM2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED66.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED250.9 ft. SSS - Surface Spalling, from 12 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE ATTACGED333.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED333.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish333.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active333.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG333.9 ft. AMH - Downstream Manhole, Survey Ends - 2:10AM

Observation photos (5)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED

    66.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Spalling, from 12 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE ATTACGED

    250.9 ft. - Surface Spalling, from 12 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE ATTACGED

Observations (13)

DistanceCodeObservation
333.5SSSBLISTERING PEELING CONCRETE SEVERE AGG ATTACHED
2SAMSEVERE AGG
250.9SSSPEELING CONCRETE SEVERE ATTACGED
0MWL
2DAGS
333.5DAGS
66.1SSSBLISTERING PEELING CONCRETE SEVERE AGG ATTACHED
333.5MGOConn. @ Mh, 3 O' Clock. Active
333.9AMH2:10AM
2SSSPEELING CONCRETE SEVERE AGG ATTACHED
333.5SAMSEVERE AGG
0MWM
0AMH1:45AM

Properties (6)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTCHED
custom_field_two
2
customer
LACSD
datetime
2022-03-17T01:44:54-07:00
documentation
MARTIN,REVELES,OLIVER111,CASTILLO
is_lateral_inspection
false