Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2022, 10:14 AM
  • 02 0923_02 0922_01112022_021858.mp4

Date
01/11/2022
W/O
926626
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00252
PipeID
P03491
Time
2:14 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9824
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION TRUNK
City
PICO RIVERA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_926626_TV02053_DEC2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
15 in.
Upstream MH
02 0923
Downstream MH
02 0922
Dir. of Survey
Downstream
Length Surveyed
41.6 ft.
Total Length
41.6 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 0923 to 02 0922
MH: 02 0923MH: 02 0922downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 09230 ft. MGO - General Observation - COCKROACHES IN MH0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start25.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES39.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish41.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0922

Observation photos (3)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    25.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
41.6AMH02 0922
0AMH02 0923
39.6DAGS
0MGOCOCKROACHES IN MH
2DAGS
0MWL
25.3CL
0MWM

Properties (7)

additional_info
630138011022201
custom_field_three
CRACK
custom_field_two
3
customer
1
datetime
2022-01-11T02:14:57-08:00
documentation
PRO PIPE
is_lateral_inspection
false