Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2022, 09:22 AM
  • J 0050_J 0048_02082022_014710.mp4

Date
02/08/2022
W/O
932167
Weather
Dry
Operator/Surveyor
J.BUENROSTRO
Sewer ID
Z00062
PipeID
P11627
Time
1:22 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9776
Sewer Name
J JOINT OUTFALL J - UNIT 2C
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Routine Assessment
Project
RFIR_WO_932167_TV05287_JAN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
J 0050
Downstream MH
J 0048
Dir. of Survey
Downstream
Length Surveyed
572.8 ft.
Total Length
572.8 ft.
Structural Index
3
Structural Quick
3V00
Structural Rating
339
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
339
Pipe schematic from manhole J 0050 to J 0048
MH: J 0050MH: J 0048downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 00500 ft. MWM - Water Mark, 40 %of cross sectional area2.3 ft. MGO - General Observation - MAG COATING4.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start569.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish572.8 ft. AMH - Downstream Manhole, Survey Ends - J 0048572.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
569.7SAP
572.8AMHJ 0048
4.3SAP
572.8MGOCONNECTION AT MH 9 O'CLOCK
0MWL
0AMHJ 0050
2.3MGOMAG COATING
0MWM

Properties (7)

additional_info
630098020722201
custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2022-02-08T01:22:10-08:00
documentation
PROPIPE
is_lateral_inspection
false