Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2022, 07:48 AM
  • 29 0193_29 0173_02032022_000701.mp4

Date
02/02/2022
W/O
936491
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01025
PipeID
P24091
Time
11:48 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9860
Sewer Name
29 28TH STREET SEWER
City
SIGNAL HILL
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
02
Purpose
Routine Assessment
Project
RFIR_WO_936491_TV29101_FEB2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0193
Downstream MH
29 0173
Dir. of Survey
Downstream
Length Surveyed
325.7 ft.
Total Length
325.7 ft.
Structural Index
3
Structural Quick
4231
Structural Rating
13
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
13
Pipe schematic from manhole 29 0193 to 29 0173
MH: 29 0193MH: 29 0173downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 01930 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area8.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES17.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES20.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"42.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"51 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"90 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"92.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"143 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"187.4 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"190.1 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"214.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES216.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"237.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"239.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"287.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"289.9 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"324.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.7 ft. AMH - Downstream Manhole, Survey Ends - 29 0173325.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    8.8 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    17.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    214.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
324.1CM
0AMH29 0193
90TFC
51TBA
0MWM
187.4TFA
0MWL
40.5TFC
20.6CM
8.8CL
237.6TFC
143TFC
325.7AMH29 0173
92.8TFC
289.9TFA
239.8TFC
216.2TBA
17.7FM
287.3TFC
42.9TFC
190.1TFC
325.7MGOCONNECTION AT MH 9 O'CLOCK
214.6FM
140.3TFC

Properties (7)

additional_info
630138020222202
custom_field_three
MULTIPLE CRACKS/FRACTURES
custom_field_two
2
customer
1
datetime
2022-02-02T23:48:19-08:00
documentation
PRO PIPE
is_lateral_inspection
false