- Date
- 02/10/2022
- W/O
- 936479
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00501
- PipeID
- P07144
- Time
- 12:15 AM
- Certificate
- U-115-06022794
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K9729
- Sewer Name
- 05 PALOS VERDES NORTH SLOPE TRUNK, SECT 1
- City
- TORRENCE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 35
- Purpose
- Routine Assessment
- Project
- RFIR_WO_936479_TV05312_FEB2022
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 21 in.
- Upstream MH
- 05 2663
- Downstream MH
- 05 1916
- Dir. of Survey
- Downstream
- Length Surveyed
- 376.6 ft.
- Total Length
- 376.6 ft.
- Structural Index
- 3
- Structural Quick
- 4J3N
- Structural Rating
- 599
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 599
Pipe schematic from manhole 05 2663 to 05 1916 Observation photos (4)

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

56.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

102.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start