Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2022, 10:37 AM
  • B 0556_B 0555_02042022_025911.mp4

Date
02/04/2022
W/O
931719
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00101
PipeID
P09103
Time
2:37 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9864
Sewer Name
B JOINT OUTFALL B - UNIT 7
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_931719_TV15226_JAN2022
Sewer Type
Gravity
Material
CIP
Shape
Circular
Height
12 in.
Width
21 in.
Upstream MH
B 0555
Downstream MH
B 0556
Dir. of Survey
Upstream
Length Surveyed
127.6 ft.
Total Length
127.6 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole B 0555 to B 0556
MH: B 0555MH: B 0556upstream0 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish0 ft. MSA - Survey Abandoned - REVERSAL COMPLETE.101.7 ft. DSC - Deposits Settled Compacted, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish118.7 ft. DSC - Deposits Settled Compacted, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start125.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start125.6 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start125.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start127.6 ft. MGO - General Observation - COCKROACHES IN MH127.6 ft. MWL - Water Level, 5 %of cross sectional area127.6 ft. AMH - Downstream Manhole, Survey Begins - B 0555127.6 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (6)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Compacted,  30 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    8.9 ft. - Deposits Settled Compacted, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Survey Abandoned - REVERSAL COMPLETE.

    127.6 ft. - Survey Abandoned - REVERSAL COMPLETE.

Observations (13)

DistanceCodeObservation
127.6SCP
127.6SSS
2SSS
127.6DAGS
25.9DSC
0MGOCOCKROACHES IN MH
0MWL
2SCP
2DAGS
0AMHB 0555
0MWM
8.9DSC
127.6MSAREVERSAL COMPLETE.

Properties (6)

additional_info
630138020322203
custom_field_two
2
customer
1
datetime
2022-02-04T02:37:47-08:00
documentation
PRO PIPE
is_lateral_inspection
false