Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 14, 2022, 07:40 AM
  • 02 1084_02 1083_01132022_235417.mp4

Date
01/13/2022
W/O
931783
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00282
PipeID
P03658
Time
11:40 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9828
Sewer Name
02 MONTEBELLO DIVERSION TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_931783_TV02212_JAN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
21 in.
Upstream MH
02 1084
Downstream MH
02 1083
Dir. of Survey
Downstream
Length Surveyed
342 ft.
Total Length
342 ft.
Structural Index
3
Structural Quick
533L
Structural Rating
350
O&M Index
2
O&M Quick
2L00
O&M Rating
134
Overall Index
2
Overall Quick
Overall Rating
484
Pipe schematic from manhole 02 1084 to 02 1083
MH: 02 1084MH: 02 1083downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 10840 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - 35% MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start79.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"129 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"276.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"278.8 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES315.1 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES326.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN328.1 ft. SRV - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES339.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish339.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish339.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish342 ft. MGO - General Observation - ROACHES @ MH342 ft. AMH - Downstream Manhole, Survey Ends - 02 1083342 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (7)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

    278.8 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

    315.1 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

    328.1 ft. - Surface Reinforcement Visible, from 09 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - ROACHES @ MH

    342 ft. - General Observation - ROACHES @ MH

Observations (20)

DistanceCodeObservation
129TF
326.3TFOPEN
339.4SSS
79.6TFC
2MGO35% MAG COAT
0AMH02 1084
0MWM
2SSS
339.4DAGS
342MGOROACHES @ MH
0MWL
342AMH02 1083
2DAGS
2SAP
276.9TFA
339.4SAP
342MGOCONN @ MH 3 O'CLOCK/ACTIVE
315.1SRV
278.8SRV
328.1SRV

Properties (7)

additional_info
630138011322201
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-01-13T23:40:37-08:00
documentation
PRO PIPE
is_lateral_inspection
false