Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2021, 09:52 AM
  • C 0568_C 0567_11162021_020413.mp4

Date
11/16/2021
W/O
921734
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00362
PipeID
P04752
Time
1:52 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9538
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_921734_TV03084_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
18 in.
Upstream MH
C 0567
Downstream MH
C 0568
Dir. of Survey
Upstream
Length Surveyed
323.7 ft.
Total Length
323.7 ft.
Structural Index
3
Structural Quick
4C2E
Structural Rating
148
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
148
Pipe schematic from manhole C 0567 to C 0568
MH: C 0567MH: C 0568upstream0 ft. AMH - Upstream Manhole, Survey Ends - C 05685.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish113.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish113.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start140.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start164.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish288.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start323.7 ft. MWM - Water Mark, 20 %of cross sectional area323.7 ft. AMH - Downstream Manhole, Survey Begins - C 0567323.7 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (3)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    35.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    183.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    210.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
183.2CL
159.3CL
318.1FM
0MWM
210.1CL
35.2CL
323.7AMHC 0568
0AMHC 0567
210.1FM
0MWL

Properties (7)

additional_info
630074111521201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-11-16T01:52:03-08:00
documentation
PROPIPE
is_lateral_inspection
false