Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2021, 09:03 AM
  • C 0566_C 0565_11162021_012134.mp4

Date
11/16/2021
W/O
921734
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00362
PipeID
P04750
Time
1:03 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9538
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_921734_TV03084_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
10 in.
Upstream MH
C 0566
Downstream MH
C 0565
Dir. of Survey
Downstream
Length Surveyed
417.5 ft.
Total Length
417.5 ft.
Structural Index
3
Structural Quick
4C3F
Structural Rating
199
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
199
Pipe schematic from manhole C 0566 to C 0565
MH: C 0566MH: C 0565downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 05660 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK5.6 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES27.7 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start32.7 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish32.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start139.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish233.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start236.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start236.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish329.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"417.5 ft. AMH - Downstream Manhole, Survey Ends - C 0565417.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

    5.6 ft. - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

    27.7 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    32.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start

    233.3 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    236.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    329.5 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (16)

DistanceCodeObservation
233.3CL
139.7FM
329.5TB
236.7CM
236.7CL
0AMHC 0566
0MWM
0MGOCONNECTION AT THE MH 3 OC'LOCK
417.5AMHC 0565
5.6FC
417.5CM
27.7FL
0MWL
0MGOCONNECTION AT THE MH 9 OC'LOCK
32.7FL
32.7FM

Properties (7)

additional_info
630074111521201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-11-16T01:03:33-08:00
documentation
PROPIPE
is_lateral_inspection
false