Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2021, 05:28 AM
  • C 0559_C 0558_11152021_214547.mp4

Date
11/15/2021
W/O
921734
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00362
PipeID
P04743
Time
9:28 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9538
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_921734_TV03084_NOV2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
C 0559
Downstream MH
C 0558
Dir. of Survey
Downstream
Length Surveyed
401.1 ft.
Total Length
401.1 ft.
Structural Index
3
Structural Quick
4C3M
Structural Rating
300
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
300
Pipe schematic from manhole C 0559 to C 0558
MH: C 0559MH: C 0558downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 05590 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES5.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start176.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start238.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish297 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish297 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start400.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish401.1 ft. AMH - Downstream Manhole, Survey Ends - C 0558

Observation photos (4)

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    2.6 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    176.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    297 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
238.8FL
2.6FL
297CM
0AMHC 0559
5.8CM
0MWL
297FM
401.1AMHC 0558
0MWM
176.1FL
400.2FM

Properties (7)

additional_info
630074111521201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-11-15T21:28:47-08:00
documentation
PROPIPE
is_lateral_inspection
false